Item
|
Unit
|
Data
|
|
Rated Voltage
|
KV
|
40.5
|
|
rated insulation leve1
|
thunder impulse withstand voltage(peak vaule) |
KV
|
185/215
|
| industrial frequency withstand voltaged(1 min) |
KV
|
95
|
|
rated current
|
A
|
1600
|
2000 |
|
Mechanical life-span
|
Times
|
3000
|
|
SF6 air'rated pressure (gage pressure when 20℃)
|
MPA
|
0.45
|
|
shutting pressure(gage pressure when 20℃)
|
MPA
|
0.45
|
|
the lowest use environment temperature
|
C
|
-30
|
|
rated short-circuit break current
|
KA
|
25
|
31.5 |
|
rated short-ciruit close current(peak value)
|
KA
|
63
|
80 |
|
rated little withstand current (heat stablized current)
|
KA
|
25
|
31.5 |
|
rated peak vaule withstand current (stabilized current)
|
KA
|
63
|
80 |
|
rated breaking-step dropout current
|
KA
|
63
|
80 |
|
rated short follow current
|
S
|
4
|
|
time of closing brake(under rated operation voltage)
|
S
|
≤0.1
|
|
time of breking brake(under rated operation voltage)
|
S
|
≤0.07
|
|
rated operation order
|
ms
|
off-0.3Son and off-180S-an and off
|
|
rated on-offone condenser bank'current
|
A
|
400
|
|
the accumulated dropout times under rated short dropout current
|
Times
|
15
|
10 |
|
annual air-leakage ratio
|
%years
|
≤1
|
|
water content of SF6 air (when 20℃)
|
PPM(V)
|
≤150
|
|
rated operation volt of CT14spring operation structure
|
V
|
~220v
|
|
volt of closing coil、opening coil
|
V
|
AC:220
|
|
DC:110 220
|
|
energy-store electric machine'volt
|
V
|
AC:220
|
|
DC:220
|
|
weight of SF6 air
|
KG
|
8
|
|
weight of circuit breaker(including operation structure)
|
KG
|
1400
|